Thermal Models

How simses couples battery heat generation to the surrounding environment — from a single constant-ambient coupling through to a containerised BESS with multi-layer walls, HVAC, and solar heat load.

Who this is for

Applied users whose studies care about temperature (degradation rates, efficiency, thermal runaway margins, HVAC sizing), and extenders plugging in new HVAC hardware or control strategies. If you can assume an isothermal cell for your study, you can skip this subsystem entirely.

Two environment models

The thermal subsystem ships two environment models that cover different levels of fidelity, wired into the rest of simses through one structural protocol.

AmbientThermalModel is the simple environment — one node per registered component, each coupled by a lumped thermal resistance to a single ambient temperature. No walls, no air volume, no HVAC. Appropriate when the thermal environment can be treated as a uniform external temperature — bench tests, first-order sanity checks before adding container physics, or deployments where the pack sits in a climate-controlled room whose temperature you already have as a time series.

ContainerThermalModel is the physics-based environment — a containerised BESS model with five coupled nodes (battery(ies), internal air, inner/mid/outer wall), an HVAC unit that injects or removes heat at the air node, and an optional solar heat load on the outer wall. Appropriate when wall conduction, air thermal mass, HVAC sizing, or diurnal external cycles matter.

Both expose the same public surface: construct, register heat-generating components via add_component(), call step(dt) in the simulation loop. What differs is the internal physics.

What a thermal step does

A simulation run is really two step-loops interleaved. On each timestep the battery generates heat — Joule dissipation plus the reversible entropic term — and writes it to state.heat. The thermal model, on its own step(dt), reads that heat from every registered component, advances each node's temperature by one Euler step, and writes the new temperature back onto the component's state.T. The next battery.step() reads the updated temperature when it evaluates OCV and Rint, and the loop continues.

Nothing in the thermal model calls battery.step(), and nothing in battery.step() calls the thermal model. The coupling is entirely through the shared mutable state — each side owns one half of the contract: battery writes heat and reads T; thermal model writes T and reads heat. This is what lets the same thermal model host a single battery, a multi-string pack, or a mix of batteries and other heat-generating components without any special cases.

from simses.thermal import AmbientThermalModel

env = AmbientThermalModel(T_ambient=25.0)
env.add_component(battery)

for t in range(n_steps):
    battery.step(power[t], dt)
    env.step(dt)                    # reads battery.state.heat, writes battery.state.T

The ThermalComponent contract

The thermal models talk to their nodes through ThermalComponent — a structural Protocol exposing exactly four members:

Member Type Direction Meaning
state.T float read / written Component temperature in °C.
state.heat float read Total internal heat generation in W (sign: + = heats the component, − possible when reversible cooling dominates).
thermal_capacity float read Lumped thermal capacity in J/K.
thermal_resistance float read Thermal resistance to the surrounding air/ambient in K/W.

A Battery satisfies this shape already, without inheritance — state.T and state.heat are fields on BatteryState, thermal_capacity and thermal_resistance are properties derived from the cell's ThermalCellProperties and effective cooling area. In principle any simses component with internal losses is a candidate thermal node: a Converter dissipates conversion losses that could be tracked as a node; a supercap or flow-battery storage could participate the same way. Today only Battery exposes all four members; adding them to another component is a small surface change that turns it into a first-class thermal node.

AmbientThermalModel

AmbientThermalModel treats every registered component as an independent node coupled to a single ambient temperature. Per-component heat balance, forward-Euler integrated:

\[ C_{\mathrm{th},i} \frac{\mathrm{d}T_i}{\mathrm{d}t} \;=\; \dot Q_{\mathrm{heat},i} \;+\; \frac{T_\mathrm{amb} - T_i}{R_{\mathrm{th},i}} \]

Left-hand side is the rate of change of the node's internal energy; the two right-hand terms are its own dissipation and the heat exchanged with the ambient through the lumped resistance. T_ambient is a public attribute — assigning to it at any step turns the model into a time-varying boundary condition driven by, e.g., a TMY weather profile.

No cross-coupling between components: two batteries in the same AmbientThermalModel influence each other only indirectly, through their shared ambient (i.e. not at all, at this level of fidelity). If node-to-node coupling matters, switch to ContainerThermalModel.

ContainerThermalModel

ContainerThermalModel models the thermal environment of a real BESS container — batteries sit in an air volume, surrounded by three wall layers (typically inner aluminium / insulation / outer steel), which in turn exchange heat with the ambient. It has more moving parts than the ambient model and is worth a short preview before the details:

  • A five-node thermal network — batteries, internal air, three wall layers — integrated forward-Euler each step against ambient and two drivers (HVAC, solar).
  • An HVAC subsystem split into a strategy (decides how much heating/cooling the container needs) and hardware (converts thermal demand into an electrical cost). Both are Protocols, so you can swap either half independently.
  • An optional solar heat load — a vectorised pipeline that pre-computes absorbed solar power on the container outer walls from a GHI time series. Feeds one driver on the thermal network.

Each of those gets its own section below.

Thermal network

Five nodes (batteries, internal air, three wall layers) and six thermal couplings. HVAC injects/removes heat at the air node; solar adds heat to the outer wall.

flowchart LR
    AMB([Ambient])
    OUT[Outer wall]
    MID[Middle wall]
    IN[Inner wall]
    AIR[Internal air]
    BAT[Battery node]

    AMB <-->|R_air_out| OUT
    OUT <-->|R_out_mid| MID
    MID <-->|R_mid_in| IN
    IN <-->|R_in_air| AIR
    AIR <-->|R_bat| BAT

    SOL([Q_solar]) --> OUT
    HVAC([Q_hvac]) --> AIR
    HEAT([Q_heat]) --> BAT

Each node has a lumped thermal capacity; each edge is a thermal resistance. Capacities are precomputed once from ContainerProperties (length × width × height × material ρ × cₚ for walls and air); resistances combine half-layer conductive plus surface convection terms. Each step(dt) evaluates the five forward-Euler node equations using current-step temperatures only (explicit scheme — stable for realistic wall thicknesses and timesteps of a few seconds).

The internal-air balance is the most useful node to reason about, since it's where HVAC lands and what the thermostat tracks:

\[ C_\mathrm{air} \frac{\mathrm{d}T_\mathrm{air}}{\mathrm{d}t} \;=\; \dot Q_\mathrm{HVAC} \;+\; \frac{T_\mathrm{in} - T_\mathrm{air}}{R_\mathrm{in\text{-}air}} \;+\; \sum_{i} \frac{T_{\mathrm{bat},i} - T_\mathrm{air}}{R_{\mathrm{bat},i}} \]

Left-hand side is the rate of change of air enthalpy; the right-hand terms are the HVAC injection, conduction from the inner wall, and the sum of heat flows from every registered battery node. Each battery node itself follows the same heat balance as in the ambient model above, just coupled to T_air instead of T_amb. The three wall-layer nodes follow analogous conduction balances between their two neighbours (and, for the outer wall, an additional solar term Q_solar and the ambient-coupling resistance).

Two external drivers are updatable between steps:

  • container.T_ambient — external temperature, e.g. driven by a weather series.
  • container.Q_solar — absorbed solar power on the outer wall, typically obtained by pre-computing a full timeseries with solar_heat_load().

Multiple components can be registered via add_component() — each becomes its own battery node, all coupled to the shared internal air. The HVAC strategy's reference temperature is the hottest registered component, so thermal management reacts to the worst-case node rather than an average.

HVAC: strategy and hardware

When HVAC is active, ContainerThermalModel.step(dt) asks the strategy for a thermal power demand — positive to heat, negative to cool — then asks the hardware model how much electrical power that demand costs. The thermal value is injected into the air node; the electrical value is stored on state.power_el (always ≥ 0) for downstream accounting (parasitic load, system-level efficiency).

The split exists because the two concerns evolve independently. A thermostat, an MPC, or a rule-based scheduler all produce the same output — a thermal power demand — but don't care what hardware executes it. Conversely, swapping a constant-COP HVAC for a temperature-dependent chiller or a heat pump changes the electrical cost per watt of cooling but leaves the control policy untouched.

ThermalManagementStrategy (the brain)

ThermalManagementStrategy is a Protocol: control(T_ref, dt) -> Q_thermal. Two implementations ship:

ThermostatStrategy is a three-state hysteresis controller — IDLE, HEATING, COOLING. It watches T_ref (the hottest battery node) and compares it to a setpoint with a symmetric dead-band of ±threshold:

  • From IDLE, it switches to HEATING once T_ref drops below T_setpoint − threshold, and to COOLING once T_ref rises above T_setpoint + threshold.
  • From either HEATING or COOLING, it returns to IDLE as soon as T_ref reaches T_setpoint.

In HEATING mode it requests +max_power thermal; in COOLING it requests −max_power; in IDLE it requests zero. The asymmetry — entry requires crossing the full threshold, exit returns at the setpoint — is what prevents short-cycling around T_setpoint.

ExternalThermalManagement is a pass-through for studies that compute HVAC power outside the simulation (optimisation, MPC, co-simulation). It stores a single Q_hvac attribute that the external controller writes before each container.step(dt), and control() returns exactly that. The container still calls the HvacModel to compute electrical draw, so the accounting stays consistent.

HvacModel (the hardware)

HvacModel is a Protocol: electrical_consumption(Q_thermal) -> float. The default implementation ConstantCopHvac applies a fixed coefficient of performance per direction:

\[ P_\mathrm{el} \;=\; \begin{cases} \dot Q / \mathrm{COP}_\mathrm{heat} & \dot Q > 0 \\[2pt] \lvert \dot Q \rvert / \mathrm{COP}_\mathrm{cool} & \dot Q < 0 \\[2pt] 0 & \dot Q = 0 \end{cases} \]

Typical defaults are COP_heating = 2.5, COP_cooling = 3.0. A real chiller is non-linear in load and ambient temperature; more detailed models implementing the same Protocol can replace this drop-in.

Solar heat load

solar_heat_load() pre-computes the absorbed solar power on the outer wall over a full timeseries in one vectorised pass, returning a pd.Series aligned with the input GHI index. The pipeline is:

  1. Astronomical solar position from day-of-year, latitude, and longitude (Spencer 1971 Fourier series — no external library).
  2. Reindl decomposition of global horizontal irradiance into direct and diffuse components via the clearness index.
  3. Per-face absorbed power on the five exposed surfaces (N, S, E, W, roof) using geometric angle-of-incidence and the outer-surface absorptivity. Vertical faces also receive ground-reflected irradiance (albedo) and isotropic sky diffuse.

The input GHI must carry a timezone-aware DatetimeIndex; the function enforces this. Because the calculation depends only on site location and container geometry — not on simulation state — it runs once before the simulation loop:

from simses.thermal.solar import SolarConfig, solar_heat_load

q_solar = solar_heat_load(
    ghi=ghi_series,                                    # pd.Series, W/m², tz-aware index
    container=container_properties,
    config=SolarConfig(latitude=48.14, longitude=11.58, azimuth=0.0),
)

for t, step in enumerate(timesteps):
    battery.step(power[t], dt)
    container.Q_solar = q_solar.iloc[t]                # feed per-step
    container.T_ambient = ambient_series.iloc[t]
    container.step(dt)

Roof is treated differently from vertical faces (full sky view, no ground-reflected component). Night-time and below-horizon rows evaluate to zero without special-casing.

State

AmbientThermalModel.state is a single field (T_ambient). ContainerThermalModel.state carries the full node picture:

Field Unit Meaning
T_air °C Internal air temperature.
T_in, T_mid, T_out °C Wall-layer temperatures.
T_amb °C External ambient (updatable driver).
Q_solar W Absorbed solar power on the outer wall (updatable driver).
power_th W HVAC thermal power delivered this step (+ heat, − cool).
power_el W HVAC electrical draw this step (≥ 0).

Battery temperatures live on each battery's own state.T, not here — registered components own their temperatures; the container only owns its environment.